HVAC

CÔNG TY TNHH THIẾT BỊ VÀ PHỤ TÙNG BÁCH KHOA

Hotline: +84 903999357

Tiếng Việt (Vietnamese)English (United Kingdom)

Thương hiệu

CMT200

Current/Voltage Selectable Output, 200 PPM Range Features
• Field selectable current or voltage outputs
• Replaceable sensor
• Field calibration kits
Approvals
• CE
Applications
• Garage ventilation
• Mechanical room monitoring
Specifications
Sensor: Field replacement electrochemical, 4 year typical lifespan
Range: 0 to 200 ppm
Coverage Area: 5000 to 7000 sq.ft.typical.
Accuracy: ±2% of reading at the time of calibration.
Output Drift: <5% per year in air.
Temperature Limits: -4 to 122°F (-20 to 50°C).
Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C).
Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent.
Response Time: < 45 seconds to 90% of final value.
Calibration: 15 turn span and zero adjustment potentiometers.
Housing: UV resistant polycarbonate
Output: Jumper selectable 4 to 20 mA (loop powered) or 2 to 10 V (load must be>50KΩ).
Power Requirements: Current Output: 18 to 28 VDC; Voltage Output:18 to 28 VDC/VAC, reverse polarity protected.
Electrical Connection: Removable terminal block, includes two PG11 and one PG 16 knockouts for conduit fitting
Weight: 0.28 (0.11 k g).
Agency Approvals: CE.
General Information
The MODEL CMT200 Carbon Monoxide Transmitter provides a field selectable current or voltage output that is proportional to the gas concentration in underground parking garages, vehicle maintenance facilities, or mechanical rooms.