Air Velocity Transmitter with Cable
For Remotely Mounting Electronic Enclosure
The Series 641RM
is the ideal instrument for monitoring air flow. This transmitter uses a heated mass flow sensor, which allows for precise velocity measurements at various flow rates and temperatures. The 641’s 16 field selectable ranges from 0-250 to 15,000 FPM (0-1.25 to 75 MPS) provide it the versatility to be selected for a multitude of pplications. The units 6' cable which connects the sensing probe with the electronic enclosure allows the enclosure to be mounted where it can be more easily accessed. Longer cable lengths are available fro ducts that are at very high elevations from the plant floor. The optional LED produces a complete, compact solution for local indication of air flow.
ACCESSORIES
A-156, Universal Mounting Plate, 1/2˝ female NPT
A-158, Split Flange Mounting Kit
A-159, Duct Mounting Gland
641-LED, Field-upgradeable LED

SPECIFICATIONS
Service:
Clean air and compatible, non-combustible gases.
Accuracy:
3% FS process gas: 32 to 122°F (0 to 50°C);
4% FS process gas:-40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).
Response Time: Flow: 1.5 seconds to 95% of final value (output filter set to minimum).
Temperature Limits:
Process: -40 to 212°F (-40 to 100°C);
Ambient: 32 to 140°F (0 to 60°C).
Pressure Limit: 100 psi (6.89 bar) maximum.
Humidity Limit: Non-condensing.
Power Requirements: 12–35 VDC, 10–16 VAC. 1.5A rating required on supply due to initial power surge drawn by transmitter.
Output Signal: 4-20 mA, isolated 24V source, 3 or 4-wire connection
Output Filter: Selectable 0.5–15 (seconds).
Loop Resistance: 600 ohms max.
Current Consumption: 300 mA max.
Electrical Connections: Screw terminal.
Mounting Orientation: Unit not position sensitive. Probe must be aligned with airflow.
Weight: 13.2 oz (374.26 g).
Cable Length: 6 ft (1.82 m).
Probe Length: 12˝ (30.48 cm) standard.
Probe Diameter: 5/16˝ (0.79 cm).
OPTIONAL DISPLAY VERSION:
Display:
4-1/2 digit 1/2˝ red LED.
Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).
Weight: 13.9 oz (394.16 g).