Cảm biến chênh áp - Series 605 - Magnehelic®

Series 605
Magnehelic® Differential Pressure Indicating Transmitter


The Series 605 Magnehelic® Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure. The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system. The easily read dial gage is complimented by the two-wire, 4-20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gage mechanical design and Series 600 transmitter technology. The two-wire design with terminal strip on the rear simplifies connection in any 4-20 mA control loop powered by a 10-35 VDC supply.

Applications:
• Monitor pressures in ducts, rooms, or total building pressures.
• Filter monitoring.
• Local indication of clean room pressures with process signal sent to control room.

Specifications:

GAGE SPECIFICATIONS
  • Service: Air and non-combustible, compatible gases.
  • Wetted Materials: Consult factory.
  • Accuracy: See Ordering page.
  • Stability: ±1% F.S./yr.
  • Pressure Limits: See Ordering page.
  • Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
  • Process Connections: 1/8" female NPT.
  • Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x 2-11/16" (68.3 mm).
  • Weight: 1 lb, 12.6 oz (811 g).
  • Agency Approvals: CE.
TRANSMITTER SPECIFICATIONS
  • Accuracy: See Ordering page (includes linearity, hysteresis, repeatability).
  • Temperature Limits: 20 to 120°F(-6.67 to 48.9°C).
  • Compensated Temperature Range: 32 to 120°F (0 to 48.9°C).
  • Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
  • Power Requirements: 10-35 VDC (2-wire).
  • Output Signal: 4 to 20 mA.
  • Zero and Span Adjustments: Protected potentiometers.
  • Loop Resistance: DC; 0-1250 ohms maximum.
  • Current Consumption: DC; 38 mA maximum.
  • Electrical Connections: Screw terminal block.
  • Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations.